Kareem Shaaban

Home / Projects / 28.8 kW hybrid

Hybrid · Mauritania

28.8 kW hybrid solar PV in Mauritania

A rooftop hybrid PV system for a private villa, combining solar with the grid and battery storage — from sizing and simulation to shop drawings and the bill of quantities.

Role: Design engineer

28.8kWp

Overview

This 28.8 kWp hybrid rooftop system was designed for a private villa in Mauritania. Forty-eight Jinko 600 W modules feed a Deye 29.9 kW three-phase hybrid inverter backed by battery storage, keeping the villa powered by solar first, with the grid and the battery as support. The work covered manual sizing and energy calculations, a PVsyst simulation of an earlier design iteration, the single-line diagram, the general layout, the shop drawing and the full bill of quantities.

Scope of work

  • Manual system sizing and energy calculations
  • PVsyst energy simulation
  • Single-line diagram (SLD)
  • General layout and arrangement
  • Shop drawing for execution
  • Bill of quantities and cable protection sizing

System layout

Indicative single-line layout: PV and grid into the Deye hybrid inverter with battery storage and load.

Key design data

ItemDetailValue
PV array48 × Jinko JKM600N-66HL4M, 600 W mono PERC28.8 kWp
Stringing3 strings × 16 modules in series3 MPPT
InverterDeye SUN-29.9K-SG01HP3, hybrid, three-phase29.9 kW AC
MPPT window150–850 V operating, 1000 V max input, 55 A max—
StorageDeye Li-ion battery, 51.2 V / 100 Ah≈5.1 kWh
Array tilt22° on a steel / galvanised sheet roof22°

String sizing was verified against the inverter limits at temperature extremes: the open-circuit voltage of one string at −5 °C stays well below the 1000 V maximum, and the operating voltage at 70 °C stays inside the MPPT window.

DC checkResultLimit
Voc per string at −5 °C825.0 V< 1000 V max ✓
Vmpp per string at 70 °C577.4 V150–850 V MPPT ✓

Design drawings

Bill of quantities

ItemDescriptionQty
PV modulesJinko JKM600N-66HL4M, 600 W mono PERC48
Hybrid inverterDeye SUN-29.9K-SG01HP3, 29.9 kW AC, 3 MPPT1
BatteryDeye Li-ion, 51.2 V / 100 Ah1
Solar DC cablePV1-F 1×6 mm², UV-resistantLot
String fuses20 A gPV, in fuse holders4
DC isolator1000 V / 32 A, pole-mounted near inverter1
DC surge protectionType II SPD, DC side1
AC breakerMCCB 40 A / 4P1
AC cable3×16 mm² copperLot
Junction boxesIP65, outdoor rated2
EarthingEarth rods with bonding to structure2
MountingSteel / GAL rails at 22° tilt on sheet roofLot

Energy simulation (PVsyst)

Deliverables

  • Sizing and energy calculations workbook
  • PVsyst simulation report
  • Single-line diagram
  • General layout drawing
  • Shop drawing for execution
  • Bill of quantities

Discuss a similar project